Tyco Simplex 2099-9XXX non-coded non-addressable manual station. Single or Double action operation. Surface or Flush mounting. High impact polycarbonate housing. Complies with ADA requirements. UL listed.

UL

2099-9754   
Favor de solicitar precio via Email   

Versión

   6 Semanas  ]
14 Variants of base SKU
Features Manual fire alarm stations for general purpose applications:
  • Operation complies with ADA requirements
  • Pull lever protrudes when alarmed
  • Break-rod is supplied, use is optional
  • Screw terminals for wiring connections
  • Tamper resistant reset key lock (keyed same as Simplex fire alarm cabinets)
Operation types include:
  • Single action
  • Double Action, Breakglass or Push Type
  • Institutional Model, key operated only
  • Optional NO GRIP Single Action Retrofit Kits are available with a more easily operated pull lever for applications where anticipated users may find the standard station lever difficult to activate
  • Optional Local Alarm cover
  • Optional pre-signal and annunciator contacts
Multiple mounting options:
  • Surface or semi-flush with standard boxes or matching Simplex boxes
  • Flush mount adapter kit
UL listed to Standard 38 Operation

Activation of the Simplex single action manual stations requires a firm downward pull to activate the alarm switch. Completing the action breaks an internal plastic break-rod which is visible below the pull lever, use is optional. The use of a break-rod can be a deterrent to vandalism without interfering with the minimum pull requirements needed for easy activation. The pull lever latches into the alarm position and remains extended out of the housing to provide a visible indication.

Double Action Stations (Breakglass) require the operator to strike the front mounted hammer to break the glass and expose the recessed pull lever. The pull lever then operates as a single action station.

Double Action Stations (Push Type) require that a spring loaded interference plate, which is marked PUSH, be pushed back to access the pull lever of the single action station.

Station reset requires the use of a key to reset the manual station lever and deactivate the alarm switch. If the break-rod is used, it must be replaced.

Station testing is performed by physical activation of the pull lever. Electrical testing can be also performed by unlocking the station housing to activate the alarm switch.

Institutional Stations activate by key operation only allowing access for manual alarms to be initiated by authorized personnel. Operation requires key insertion and opening of the station cover.

Single Action Station NO GRIP Retrofit Kit 4099-9805. For applications such as California Building Code, Title 24, which requires "Controls and operating mechanisms shall be operable with one hand and shall not require tight grasping, pinching or twisting of the wrist" the model 4099-9805 Retrofit kit provides a more easily operated pull lever compared to standard stations.

Pre-Signal Option activates when the lever is pulled. General alarm initiation requires a key to activate a keyswitch located behind the pull lever.

Station Reset requires the use of a key to reset the manual station lever and deactivate the alarm switch. If the break-rod is used, it must be replaced.

Testing requires physical activation of the pull lever, except for institutional stations.

Specifications
Wire connectionsScrew terminal for in/out wiring, for 18 AWG to 14 AWG wire
UL listed temperature range32°F to 120°F (0°C to 49°C) intended for indoor operation
Humidity rangeUp to 93% RH at 100°F (38°C)
Housing colorRed with white raised lettering
MaterialHousing and pull lever are high impact polycarbonate
Pull lever colorWhite with red raised lettering
Housing dimensions5 in. H x 3 3/4 in. W x 1 in. D (127 mm x 95 mm x 25 mm)
Export Info
Fabricado enMexico
Codigo Arancelario85311001

 Solicitar Info/Cotizacion
 Descuento en Reventa y Vol
 Costo del Flete

Opciones B2B: #Order de Compra, uso de cuenta de envio propia y compra exenta de impuesto
Opciones de Pago: Tarjeta de Credito, Tarjeta de Credito por Telefono, PAYPAL, Transferencia, Deposito, Cheque y Orden de Pago

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

> CALL POINTS :    1 Articulos encontrados.
4099-9004
(6848)

SIMPLEX TYCO  4099-9004

Tyco Simplex 4099-9004 addressable manual station with communication module for IDNet or MAPNET II. LED indicator. Breakglass or push operation. Surface or Flush mounting. NEMA 1. Complies with ADA requirements. UL listed.

Aviso de Cookies

Esta tienda en línea utiliza cookies para recordar a los usuarios, permitir el pago y recopilar información agregada que nos permite analizar los patrones de tráfico en nuestro sitio (no se almacena información personal). Para más información puedes leer nuestra Política de Privacidad.