SIMPLEX TYCO   4906-9102

SKU# (6851)



SIMPLEX TYCO 4906-9102

ALARM SIGNAL DEVICES / INDOOR
HORNS

  • DESCRIPCION
  • CARACTERISTICAS
  • ESPECIFICACIONES
  • LITERATURA
Tyco Simplex 4906-91XX TrueAlarm Non-Addressable multi-candela high intensity Strobe. Ceiling-Mounted. 24VDC. 1 Hz. 15, 30, 75, or 110 candela intensity selectable. High impact flame retardant housing. NEMA 1. Complies with ADA requirements. UL listed.

4906-9102   
Favor de solicitar precio via Email   

Versión

   4 Semanas  ]
Features Visible only (V/O) 24 VDC notification appliances with high output xenon strobe, available for wall or ceiling mount:
  • Intensity is selectable as 15, 30, 75, or 110 candela with visible selection jumper secured behind strobe housing
  • Operation is compatible with ADA requirements (refer to Installation Reference, Surface or Semi-Flush Wall Mounting)
  • Polarized input allows connection to compatible reverse polarity, supervised notification appliance circuit (NAC)
  • Regulated circuit design ensures consistent flash output and provides controlled inrush current
  • Rugged, high impact, flame retardant thermoplastic housings are available in red or white with clear lens
  • Listed to UL 1971 and ULC S526
  • NEMA 1 rated. See Product Selection for more information
Strobes provide synchronized flash for use with:
  • Simplex fire alarm control panels with NACs selected to provide strobe synchronization or SmartSync two-wire control
  • 4009 IDNet NAC Extenders
  • Separate strobe Synchronization Modules that are available for Class B or Class A operation
  • Separate SmartSync Control Modules (SCMs) that provide Class B or Class A output from conventional NAC inputs
Strobe housings provides flexible, easy, and convenient semiflush or surface wall mounting:
  • Rear of housing does not extend into box
  • Wall mount strobes easily mount to single gang, double gang, or 4-inch square outlet box
  • Ceiling mount strobes mount to single gang boxes
Optional adapters and wire guards:
  • Wall mount strobe adapters are available to cover surface mounted electrical boxes and to adapt to 2975-9145 boxes
  • UL listed red wire guards are available for wall or ceiling mount strobes*
Description

Multi-Candela TrueAlert synchronized strobes provide convenient installation to standard electrical boxes. The enclosure designs are both impact and vandal resistant and provide a convenient strobe intensity selection. Since each model can be selected for intensity output, on-site model inventory is minimized and changes encountered during construction can be easily accommodated.

Ceiling mount strobes install using standard single gang electrical boxes. Color choice is determined by model number.

Strobe Intensity Selection

Proper selection of visible notification is dependent on occupancy, location, local codes, and proper applications of: the National Fire Alarm Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).

Synchronized Strobes

Multiple Strobes. When multiple strobes and their reflections can be seen from one location, synchronized flashes reduce the probability of photo-sensitive reactions as well as the annoyance and possible distraction of random flashing. These multi-candela strobes are synchronized over a two-wire circuit when connected to compatible NACs, to compatible Synchronized Flash Modules, or to SmartSync Control Modules.

SmartSync Two-Wire Control

Some applications desire the audible notification appliances to be capable of being silenced before the alarm condition is reset (on-until- silenced) while the visible notification appliances are kept activated until the alarm condition is reset (on-until-reset). SmartSync operation mode provides this function using a single circuit (two-wire operation).

Specifications
Rated Voltage RangeRegulated 24 VDC; see Note 1 below
Flash Rate1 Hz
Synchronized NAC LoadingUp to 35 synchronized strobes maximum per NAC
Temperature Range32° to 122° F (0° to 50° C)
Humidity Range10% to 93%, non-condensing at 100° F (38° C)
ConnectionsTerminal blocks for 18 AWG to 12 AWG (0.82 mm to 3.31 mm ); two wires per terminal for in/out wiring
Housing Dimensions (with lens)4-3/4" L x 2-5/16" W x 2-5/8" D (121 mm x 75 mm x 67 mm)
Maximum RMS Current Rating per Strobe Setting (see Note 2 below)15 cd: 75mA
30 cd: 125mA
75 cd: 233mA
110 cd: 316mA

 Solicitar Info/Cotizacion
 Descuento en Reventa y Vol
 Costo del Flete

Opciones B2B: #Order de Compra, uso de cuenta de envio propia y compra exenta de impuesto
Opciones de Pago: Tarjeta de Credito, Tarjeta de Credito por Telefono, PAYPAL, Transferencia, Deposito, Cheque y Orden de Pago

Checkout with Paypal Visa MasterCard Amex Checkout with Wire Transfer Electronic Payment

Aviso de Cookies

Esta tienda en línea utiliza cookies para recordar a los usuarios, permitir el pago y recopilar información agregada que nos permite analizar los patrones de tráfico en nuestro sitio (no se almacena información personal). Para más información puedes leer nuestra Política de Privacidad.