GENERAL SPECIFICATIONS |
Spectral Response | UV 0.185-0.260 μm |
Detection Range (at highest Sensitivity Setting
for 1ft2 (0.1m2) pan fire) |
Fuel |
ft / m |
n-Heptane |
50 / 15 |
Gasoline |
50 / 15 |
Diesel Fuel |
37 / 11 |
JP5 |
37 / 11 |
Kerosene |
37 / 11 |
Ethanol 95% |
37 / 11 |
Methanol |
37 / 11 |
IPA (Isopropyl Alcohol |
37 / 11 |
Hydrogen |
33 / 10 |
Methane* |
40 / 12 |
LPG * |
40 / 12 |
Polypropylene Pellets |
18 / 5 |
Office Paper |
20 / 6 |
* 20" (0.5m) high, 8" (0.2m) width plume fire |
|
Response Time |
Typically 3 seconds
|
Adjustable Time Delay | Up to 30 seconds
|
Sensitivity Ranges | 1 ft2 (0.1m2) n-heptane pan fire from 50 ft (15m)
|
Field of View | Horizontal 100º; Vertical 95º
|
Built-in-Test (BIT) | Automatic (and Manual)
|
Temperature Range | Operating: -67ºF to +167ºF (-55ºC to +75ºC) Option: -67ºF to +185ºF (-55ºC to +85ºC) Storage: -67ºF to +185ºF (-55ºC to +85ºC)
|
Humidity | Up to 95% non-condensing (withstands up to 100% RH for short periods)
|
Heated Optics | To eliminate condensation and icing on the window
|
ELECTRICAL SPECIFICATIONS |
Operating Voltage | 24 VDC nominal (18-32 VDC)
|
Power Consumption | Standby: Max. 90mA (110mA with heated window) Alarm: Max. 130mA (160mA with heated window)
|
Cable Entries | 2 x 3/4" - 14NPT conduits or 2 x M25 x 1.5 mm ISO
|
Wiring | 12 - 22AWG (2.5mm 2 - 0.3mm 2)
|
Electrical Input Protection | According to MIL-STD-1275B
|
Electromagnetic Compatibility | EMI/RFI protected to EN61326-3 and EN61000-6-3
|
Electrical Interface | The detector includes twelve (12) terminals with five (5) wiring options (factory set)
|
OUTPUTS |
Relays | Alarm, Fault and Auxiliary SPST volt-free contacts rated 5A at 30 VDC or 250 VAC.
|
0-20mA (stepped) | Sink (source option) configuration
Fault: 0 +1mA
BIT Fault: 2mA ± 10%
Normal: 4mA ± 10%
Warning: 16mA ± 5%
Alarm: 20mA ± 5%
Resistance Loop: 100-600 Ω |
HART Protocol |
Optional HART communications on the 0-20mA analog current (FSK) - used for maintenance,
configuration changes and asset management, available in mA source output wiring options
|
RS-485 | RS-485 Modbus compatible communication link that can be used in computer controlled installations
|
MECHANICAL SPECIFICATIONS |
Materials Enclosure options | - Stainless Steel 316L with electro polish finish - Heavy duty copper free aluminum (less than 1%), red epoxy enamel finish |
Mounting | Stainless Steel 316L with electro polish finish
|
Dimensions | Detector 4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)
|
Weight | Detector (St.St.): 6.1 lb (2.8 kg) Detector, aluminum: 2.8 lb (1.3 kg) Tilt mount: 2.2 lb (1.0 kg)
|
Environmental Standards | Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
|
Water and Dust | IP66 and IP67 per EN60529, NEMA 250 6P
|
APPROVALS |
Hazardous Area |
ATEX and IECEx |
Ex II 2 GD, |
|
|
Ex de IIC T5 (-55oC to +75oC)
|
Ex de IIC T4 (-55oC to +85oC)
|
|
Ex tD A21 IP66/X7 T 95oC
|
Ex tD A21 IP66/X7 T 105oC
|
FM / FMC / CSA |
Class I Div. 1, Groups B, C & D
|
|
|
Class II/III Div. 1, Groups E, F & G
|
|
|
Performance | EN54-10 (LPCB) FM-3260 (FM)
|
Reliability | IEC61508 - SIL2 (TUV) - model 40/40UB only
|
ACCESSORIES |
Fire Simulator | 20/20-311
|
U-Bolt/Pole Mount | 789260-2 (2" pole) 789260-1 (3" pole)
|
Mini Laptop Kit
| 777820
|
Laser Pointer | 777166
|
Tilt Mount | 40/40-003 |
Weather Protector | 777163 |
Duct Mount | 777670 |
USB RS485 Harness Kit | 794079-5 |
Air Shield | 777161 |